Permit Number: T08CM02728
Parcel: 13414002M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02728
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2008 STEVE SHIELDS ZONING REVIEW Approved
08/08/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02728 8/8/08

1. Available fault current for a 1200A 120/201V service is 75,100, not 55,600A.
2. If equipment on power plan is existing, please note it as such.
08/08/2008 ROBERT SHERRY WATER REVIEW Approved
08/08/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/08/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
08/08/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/08/2008 PAUL MACHADO ENGINEERING REVIEW Approved
08/08/2008 RBROWN1 ADA REVIEW Passed
08/08/2008 RONALD BROWN ZONING HC SITE REVIEW Passed
08/27/2008 CPIERCE1 FIRE REVIEW Needs Review
08/27/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review