Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02728
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/08/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/08/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02728 8/8/08 1. Available fault current for a 1200A 120/201V service is 75,100, not 55,600A. 2. If equipment on power plan is existing, please note it as such. |
| 08/08/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/08/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/08/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 08/08/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/08/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 08/08/2008 | RBROWN1 | ADA | REVIEW | Passed | |
| 08/08/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Passed | |
| 08/27/2008 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 08/27/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |