Permit Number: T08CM02704
Parcel: 116110060

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02704
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2008 DAVID RIVERA ZONING REVIEW Approved
08/06/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comments:
1. Show how fan coil 10 is to be supported.
2. Provide secondary condensate drainage.
3. Revise the size of the condensate piping to comply with
the sizing requirements of Section 307.2.2, IMC 2006, as amended by the City of Tucson.
08/06/2008 RBROWN1 ADA REVIEW Passed
08/06/2008 LOREN MAKUS ENGINEERING REVIEW Approved
08/06/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/06/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the pipe sizes, loads, and developed lengths for the gas piping.
08/06/2008 DAVE MANN FIRE REVIEW Approved
08/06/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
08/07/2008 CPIERCE1 WWM REVIEW Needs Review
08/07/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/07/2008 CPIERCE1 WATER REVIEW Needs Review
08/07/2008 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review