Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02703
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2008 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/07/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/07/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/07/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 08/07/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the water heater support. 2. Provide a vacuum relief for the water heater. 3. The use of a ¾" supply to a urinal will result in a water velocity exceeding 8 FPS (1 GPF, 4 seconds duration). |
| 08/07/2008 | CPIERCE1 | WWM | REVIEW | Needs Review |