Permit Number: T08CM02703
Parcel: 116110060

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02703
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2008 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/07/2008 ROBERT SHERRY WATER REVIEW Approved
08/07/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/07/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/07/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the water heater support.
2. Provide a vacuum relief for the water heater.
3. The use of a ¾" supply to a urinal will result in a water velocity exceeding 8 FPS (1 GPF, 4 seconds duration).
08/07/2008 CPIERCE1 WWM REVIEW Needs Review