Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02703
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2008 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/06/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how fan coil 9 is to be supported. 2. Provide secondary condensate drainage. 3. Show how the size of the condensate piping from FC-5 through FC-6 complies with the sizing requirements of Section 307.2.2, IMC 2006, as amended by the City of Tucson. 4. Is the rectangle located west of FC-6 and labeled with keynote #2 actually a condensate pump? 5. The calculated required outside air for AC-1 (2008 CFM) is incorrect per Section 403.3.2, IMC 2006 and exceeds the 2050 CFM noted in the outside air calculation. (Coordinate the scheduled outside air quantity for AC-1 with outside air calculation.) |
| 08/06/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide the pipe sizes, loads, and developed lengths for the gas piping. |
| 08/06/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/06/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/07/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 08/07/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/07/2008 | CPIERCE1 | WATER | REVIEW | Needs Review | |
| 08/07/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/07/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 08/07/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 08/07/2008 | ENEWCOM1 | ADA | REVIEW | Passed |