Permit Number: T08CM02703
Parcel: 116110060

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02703
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2008 DAVID RIVERA ZONING REVIEW Approved
08/06/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how fan coil 9 is to be supported.
2. Provide secondary condensate drainage.
3. Show how the size of the condensate piping from FC-5 through FC-6 complies with the sizing requirements of Section 307.2.2, IMC 2006, as amended by the City of Tucson.
4. Is the rectangle located west of FC-6 and labeled with keynote #2 actually a condensate pump?
5. The calculated required outside air for AC-1 (2008 CFM) is incorrect per Section 403.3.2, IMC 2006 and exceeds the 2050 CFM noted in the outside air calculation. (Coordinate the scheduled outside air quantity for AC-1 with outside air calculation.)
08/06/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the pipe sizes, loads, and developed lengths for the gas piping.
08/06/2008 LOREN MAKUS ENGINEERING REVIEW Approved
08/06/2008 DAVE MANN FIRE REVIEW Approved
08/07/2008 CPIERCE1 WWM REVIEW Needs Review
08/07/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/07/2008 CPIERCE1 WATER REVIEW Needs Review
08/07/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/07/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
08/07/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/07/2008 ENEWCOM1 ADA REVIEW Passed