Permit Number: T08CM02691
Parcel: 122160020

Address:
3528 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02691
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2008 TERRY STEVENS ZONING REVIEW Approved
08/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/05/2008 RBROWN1 ADA REVIEW Passed
08/05/2008 ROBERT SHERRY WATER REVIEW Approved
08/05/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/05/2008 PAUL MACHADO ENGINEERING REVIEW Approved
08/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/05/2008 DAVE MANN FIRE REVIEW Approved
08/05/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
08/08/2008 GERRY KOZIOL WWM REVIEW Approved
08/08/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM02691 8/5/08

1. Provide a panel and circuit number for new ceiling fans.
2. Provide switch/disconnecting means for the ceiling fans, per NEC 430 Part IX.
3. Show panel load calculations per NEC 220.
4. 2006 IECC requires that a change on occupancy resulting in any increase in demand for fossil fuel or electrical power shall comply with that Code. This may be satisfied by simply documenting the volt-amperes of electrical load removed, and comparing it to the VA added for the fan.