Permit Number: T08CM02690
Parcel: 132130480

Address:
1001 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02690
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2008 DAVE MANN FIRE REVIEW Approved
08/11/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A100; DEMOLITION/FLOOR PLAN: ARE NOTES 12, 16, AND 17 TO BE OMITTED? NOT LOCATED ON PLANS.
2. SHEET A100; DEMOLITION/CEILING PLAN: IS NOTE 15 TO BE OMITTED? NOT LOCATED ON PLANS.
08/13/2008 GERRY KOZIOL WWM REVIEW Approved
08/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide a cleanout for the foot vent. Reference: Section 909.0, UPC 2006.
3. Provide a cleanout for the new hand sink and for the two new floor sinks. Reference: Section 707.4, UPC 2006.
4. Show how the new drainage piping relates to the existing drainage piping in the building. The instruction to "connect to nearest existing sanitary piping of equal or greater size", is not adequate to ensure compliance with the drainage pipe sizing shown in Table 7-5, UPC 2006.
08/19/2008 ROBERT SHERRY WATER REVIEW Approved
08/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the reference to a "water-cooled condenser" and to the cooling coils in the beverage system Distribution schematic. If they exist, show that the systems comply with Section 1201.3, IMC 2006, as amended by the City of Tucson.
08/22/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project; T08CM02690
1001 E Benson Hwy
TI Remodel

This plan has been denied for the following:
1. Provide the location for the new panel C on the electrical drawing , this location to be noted on plan even if EC
and McDonald rep have to verify.
2. Provide the total load calculation for the MDP with new panel C included for verification of total load.


Ray T Majuta
Elect Plan Check
DSD<Tucson
520-837/4988
8/21/08