Permit Number: T08CM02685
Parcel: 10321029W

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02685
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/25/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/25/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the design of the drainage piping for the three new floor sinks. Provide a vent for each fixture. Show the size of the existing building drain at the point of connection. Reference: Sections 707.4, 901.0, and 1001.1, UPC 2006.
09/26/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
09/30/2008 SUE REEVES REJECT SHELF Completed