Permit Number: T08CM02685
Parcel: 10321029W

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02685
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2008 DAVE MANN FIRE REVIEW Approved
08/08/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A100; FLOOR PLAN: COULD NOT LOCATE NOTE 7b ON PLAN.
08/19/2008 ROBERT SHERRY WATER REVIEW Approved
08/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide a cleanout for the foot vent. Reference: Section 909.0, UPC 2006.
3. Revise the design of the drainage piping for the three new floor sinks. Reference: Sections 707.4, 901.0, and 1001.1, UPC 2006.
4. Show how the new drainage piping relates to the existing drainage piping in the building. The instruction to "connect to nearest existing sanitary piping of equal or greater size", is not adequate to ensure compliance with the drainage pipe sizing shown in Table 7-5, UPC 2006.
08/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the reference to a "water-cooled condenser" and to the cooling coils in the beverage system Distribution schematic. If they exist, show that the systems comply with Section 1201.3, IMC 2006, as amended by the City of Tucson
08/20/2008 GERRY KOZIOL WWM REVIEW Approved
08/29/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project; T08CM02685
2250 W Ironwood Hills
Interior Remodel

1. Provide the location for new Panel C on the electrical drawing.
2. Provide the total load calculation for MDP including Panel C for total for verification of total.

Ray T Majuta
Electrical Plan Check
DSD City of Tucson
520-837/4988
9/02/08

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
09/15/2008 SUE REEVES REJECT SHELF Completed