Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM02681
Parcel: 13705501Q

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02681
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2008 DAVE MANN FIRE REVIEW Approved
08/06/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A100; DEMOLITION/FLOOR PLAN: NOTE 16 INDICATED ON PLANS IS NOT IN KEYED NOTES. CLARIFY.
2. SHEET A100; FLOOR PLAN: COULD NOT LOCATE NOTE 7B ON PLAN. CLARIFY.
08/18/2008 ROBERT SHERRY WATER REVIEW Approved
08/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide a cleanout for the foot vent. Reference Section 909.0, UPC 2006.
3. Provide a cleanout for the new hand sink and for the new floor sink. Reference: Section 707.4, UPC 2006.
4. Show how the new drainage piping relates to the existing drainage piping in the building. The instruction to "…connect to nearest existing sanitary piping of equal or greater size", is not adequate to ensure compliance with the drainage pipe sizing shown in Table 7-5, UPC 2006.
5. The use of plastic tubing for indirect waste drainage beyond the limits of the appliance (plumbing key note 13, P100) is not allowed. Reference Sections 701.1 and 803.0, UPC 2006.
08/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the reference to a "water-cooled condenser" and to the cooling coils in the beverage system Distribution schematic. If they exist, show that the systems comply with Section 1201.3, IMC 2006, as amended by the City of Tucson
08/22/2008 GERRY KOZIOL WWM REVIEW Approved
08/25/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T08CM02681
1187 W Irvington Rd
TI Remodel


This plan has been denied for the following,
1. Provide the location for the new panel C on the electrical drawing, this location to be noted on even if EC and McDonald rep to verify.
2.Provide the total load calculation for the MDP with new panel C included for verification of total load.



Ray T Majuta
Electrical Plan Check
DSD Tucson
520-837/4988
8/25/08