Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02681
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
08/06/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A100; DEMOLITION/FLOOR PLAN: NOTE 16 INDICATED ON PLANS IS NOT IN KEYED NOTES. CLARIFY. 2. SHEET A100; FLOOR PLAN: COULD NOT LOCATE NOTE 7B ON PLAN. CLARIFY. |
08/18/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/18/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006. 2. Provide a cleanout for the foot vent. Reference Section 909.0, UPC 2006. 3. Provide a cleanout for the new hand sink and for the new floor sink. Reference: Section 707.4, UPC 2006. 4. Show how the new drainage piping relates to the existing drainage piping in the building. The instruction to "…connect to nearest existing sanitary piping of equal or greater size", is not adequate to ensure compliance with the drainage pipe sizing shown in Table 7-5, UPC 2006. 5. The use of plastic tubing for indirect waste drainage beyond the limits of the appliance (plumbing key note 13, P100) is not allowed. Reference Sections 701.1 and 803.0, UPC 2006. |
08/18/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the reference to a "water-cooled condenser" and to the cooling coils in the beverage system Distribution schematic. If they exist, show that the systems comply with Section 1201.3, IMC 2006, as amended by the City of Tucson |
08/22/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
08/25/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T08CM02681 1187 W Irvington Rd TI Remodel This plan has been denied for the following, 1. Provide the location for the new panel C on the electrical drawing, this location to be noted on even if EC and McDonald rep to verify. 2.Provide the total load calculation for the MDP with new panel C included for verification of total load. Ray T Majuta Electrical Plan Check DSD Tucson 520-837/4988 8/25/08 |