Permit Number: T08CM02679
Parcel: 10602282B

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM02679
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 9-04-08
Activity: T08CM02679
Address: 38 W. Prince Rd.
Applicant: Prince Mobile Home Park

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

INCLUSIVE HOME DESIGN: (references taken from ANSI 117.1-1998 as amended)
3. Provide an accessible route from the public way extending throughout the entire first floor (except for exempt areas as defined in section 1003.3), 1003.2.
4. Vertical changes in floor elevation may not exceed ¼ inch (½ inch when beveled), 1003.4.
5. Thresholds may not exceed ½ inch in height, 404.2.5.
6. All door hardware must be lever-type or otherwise usable without tight grasping or twisting of the wrist, 404.2.7.
7. Door openings shall have a net width of not less than 30 inches, 1003.5.2.1.
8. Provide all switches, receptacles, and controls within 48 inches of the floor but not less than 15 inches above the floor, 1003.9.
9. Provide blocking in bathrooms for future installation of grab bars around: toilets, showers, and bathtubs, 1003.11.2.

FLOOR PLANS:
10. A landing or floor surface is required at all exterior doors, R311.4.3.

PLUMBING PLAN:
11. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10.
12. Provide a fuel gas appliance schedule, R106, M1302.1.

MECHANICAL PLAN:
13. Show dryer vent size and location for venting to exterior (max 25' w/bend reductions), M1502.2, M1502.6.
14. Show supply and return air ducts with a minimum R-8 insulation, R1103.2.1.

OUTDOOR LIGHTING CODE
15. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.

INTERNATIONAL ENERGY CONSERVATION CODE:
16. Specify the "R" value of the insulation, as well as the "U" factor and the solar heat gain coefficient of the windows and doors. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1.