Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM02669
Parcel: 123051630

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM02669
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2008 GERRY KOZIOL WWM REVIEW Approved
08/27/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T08CM02669

9/02/08 85 N.SIERRA VISTA DR.



PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, ENERGY, AND ELECTRICAL. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

4. LIST THE SQUARE FOOTAGES FOR ALL THE FOLLOWING AREAS SEPARATELY ON THE DRAWINGS:
- LIVABLE AREA
- GARAGE
- PORCH/PATIO COVERS
- DECKS

5. ALL ENGINEERS AND ARCHITECTS INVOLVED IN THE DESIGN OF THE STRUCTURE ARE TO SEAL THE
RELATED SHEETS OF PLANS, DETAILS AND CALCULATIONS. THIS IS IN ACCORDANCE WITH THE RULES OF
THE STATE BOARD OF TECHNICAL REGISTRATION.

STRUCTURAL PLANS:


1. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS. ALSO, THE ENGINEER OF RECORD SHALL REVIEW AND "SHOP DRAWING" STAMP APPROVAL ON TRUSS CALCULATIONS.

SECTIONS - DETAILS - MISC. NOTES:

1. 220 / A-10 ; PLEASE SHOW THE 4X8 RIDGE BEAM INCORPORATION INTO THE TRUSSES. 229/ / A-10 ?

PLUMBING PLANS:

1. PLUMBING FIXTURE SCH. / P-2 ; THE FIXTURE UNITS CITED DON'T APPEAR TO BE PER UPC TABLE 6-5. (CLOTHES WASHER , LAUNDRY TUB, BATH TUB / SHOWER, SHOWER)

2. PLUMBING FIXTURE SCH. / P-2 ; PLEASE REFLECT THE TWO SHOWER HEADS IN THE MASTER SHOWER IN THE FIXTURE SCHEDULE.



3. PLEASE PROVIDE WATER HAMMER ARRESTORS ON QUICK CLOSING VALVED APPLIANCES. UPC 609.10 , IRC P2903.5

4. ½" SUPPLYING TWO SHOWER HEADS IN THE MASTER SHOWER @ 2 FU EACH APPEARS TO BE UNDERSIZED. 310' @ 64 PSI ½"= 1 FU USING 400' OR 1 FU USING 300'.

5. IS THE EXISTING GAS WATER HEATER SUPPLIED WITH 1" COLD WATER?

6. PLEASE SHOW THE HOSE BIBS. IS THE WATER DISTRIBUTION SYSTEM SIZED TO CARRY THE HOSE BIBS?

7. THE GAS DEMAND TABLE LISTS THE GAS PACK AS 60M BTUH BUT THE MECHANICAL EQUIPMENT SCHEDULE LISTS IT AT 70M BTUH. THE ¾" GAS IS OKAY EITHER WAY. PLEASE RESOLVE.

8. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AND LINE AT TANKLESS WATER HEATERS.

9. INDICATE THE ROUTE OF THE PRESSURE AND TEMPERATURE LINES FROM THE WATER HEATERS.

MECHANICAL PLANS:

1. PLEASE DOUBLE CHECK THE 12" ROUND RETURN AIR DUCTFROM THE 3 TON UNIT. IT APPEARS TO BE UNDERSIZED PER M1403 BUT MANUAL D MAY ALLOW IT.

ELECTRICAL PLANS:

1. LIGHT FIXTURES OVER SHOWERS AND OVER TUBS WITH SHOWER HEADS ARE REQUIRED TO BE LISTED AS APPROVED FORM USE IN WET AREAS. PLEASE NOTE, THE SYMBOLS LEGEND LISTS THEM AS DAMP USE FIXTURES.

2. ARE THE DEVICES WITHOUT CIRCUIT NUMBERS (LIVING ROOM, SUN ROOM)EXISTING OR SHOULD THEY BE INCLUDED IN THE CIRCUITRY?

3. PROVIDE ELECTRIC LOAD CALCULATIONS FOR SUB-PANEL D. (A/C #1, BBH, POINT OF USE W.H.,GENERAL LIGHTING)

4. PLEASE CHECK THE REQUIRED VOLTAGE FOR P-6. 120V. OR 230V.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910

Final Status

Task End Date Reviewer's Name Type of Review Description
09/23/2008 CPIERCE1 OUT TO CUSTOMER Completed
09/23/2008 SUE REEVES REJECT SHELF Completed