Permit Number: T08CM02665
Parcel: 13338005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02665
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET CS-01; PROJECT DATA: OCCUPANCY GROUP IS A-2 PER IBC CHAPTER 3.
2. SHEET A-00; TOILET ROOM UPGRADES PLAN 3/TOILET ROOM DIMENSIONS 4: RESTROOMS DO NOT MEET REQUIREMENTS OF ICC/ANSI A117.1-2003, CHAPTER 6.
3. SHEET A-00; PLAN 3: SCALE IS NOT 1 1/2" = 1'-0".
4. SHEET A-00; RESTROOM SIGNAGE 3a: CURRENT ICC/ANSI A117.1 IS 2003.
5. SHEET A-00; PLAN 3; REFERENCE TO IBC 3409.6: THIS SECTION REFERS TO "TECHNICALLY INFEASIBLE", NOT READILY ACHIEVABLE. FROM THE FLOOR PLAN ON SHEET A-01, IT APPEARS IT WOULD BE TECHNICALLY FEASIBLE TO MAKE THE RESTROOMS ACCESSIBLE (PROVIDE ENLARGED, DIMENSIONED PLAN). DO NOT INDICATE THE RESTROOMS ARE ACCESSIBLE (REMOVE SIGNAGE) UNLESS THEY ARE ENLARGED TO MEET ACCESSIBILITY REQUIREMENTS.
6. PER IBC 3409.7, GIVE A PROJECT COST BREAKDOWN INDICATING COST OF ACCESSIBILITY ALTERATIONS (MAXIMUM REQUIREMENT OF 20%).
7. REMOVE NOTES/INDICATIONS ON ALL SHEETS CONCERNING ACCESSIBLE TOILETS UNLESS THE RESTROOMS ARE ENLARGED TO MEET ACCESSIBILITY REQUIREMENTS.
8. SHEET A-03; EQUIPMENT PLAN: REMOVE REFERENCE TO ADAAG 7.2 (AT ACCESSIBLE COUNTER). USE ANSI REFERENCE.
08/05/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/05/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS FOR ACCESSIBILITY ISSUES
08/07/2008 DAVE MANN FIRE REVIEW Approved
08/13/2008 GERRY KOZIOL WWM REVIEW Approved
08/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the connection of the existing 3-compartment sink and grease trap noted on sheet MP-01: "2 compartments of 3 compartment sink are indirect drained to floor sink receptor & grease trap". Only the sanitizing compartment of a 3-compartment sink is to be indirectly wasted and a floor sink may not be connected to a grease trap. Reference: Sections 103.2.3, 801.2, and 1014.2.1, UPC 2006.
08/18/2008 ROBERT SHERRY WATER REVIEW Approved
08/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the nature of the specified 4" oven vent shown on sheet MP-01. Reference: Section 106.3.1, IMC 2006
08/21/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2008 DELMA ROBEY OUT TO CUSTOMER Completed