Permit Number: T08CM02663
Parcel: 13631002G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02663
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 4110 S. Houghton
T08CM02663
Cell Tower (1st Review)

TRANSMITTAL DATE: December 9, 2008

1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The plan must be approved and stamped by the Special Exception Section prior to approval by Zoning.

3. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\celltower\t08cm02663.doc
12/09/2008 JAY HOGAN COMMUNICATIONS REVIEW Passed
12/09/2008 Michael Wyneken ZONING-CITY HALL REVIEW Denied 1) Provide results of archeaological survey per condition 3 of M&C ord. no. 10564.

2) Show locations of two live Saguaros to be planted in vicinity of antennas, per ord. condition 12. Show locations on plans and include planting detail for landscape review.
12/18/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 1. ALL LETTERING IS NOT 1/8" TALL. A WRITTEN APPEAL FOR 3/32" LETTERING MUST BE APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING.
2. PREVIOUS COMMENT 2: THE SPECIAL INSPECTION FORM YOU SUBMITTED HAS AN INDIVIDUAL LISTED WHO IS NOT ON THE CITY OF TUCSON APPROVED LIST.
3. PREVIOUS NOTE 5: THE CITY OF TUCSON REQUIRES DUPONT BUILDINGS, INC., TO DESIGN THIS STRUCTURE PER THE 2006 INTERNATIONAL BUILDING CODE.
4. PREVIOUS NOTE 6: THE CITY OF TUCSON REQUIRES DUPONT BUILDINGS, INC., TO DESIGN FOUNDATIONS FOR THEIR STRUCTURE USING THE GEOTECHNICAL REPORT REFERENCED ON SHEET SP-2.
5. CALCULATIONS FOR THE DUPONT BUILDING ARE STAMPED, SIGNED, AND DATED IN AUGUST OF 2004. THESE CALCULATIONS MUST BE UPDATED USING THE 2006 INTERNATIONAL BUILDING CODE AND RESTAMPED, RESIGNED, AND CURRENTLY DATED BY A LICENSED ENGINEER.