Permit Number: T08CM02662
Parcel: 136086010

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM02662
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2009 DAVE MANN FIRE REVIEW Approved
06/02/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 6-05-09
Activity: T08CM02662
Address: 10251 E. Discovery Dr.
Applicant: Terry Borrotz

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FLOOR PLANS:
3. Provide layout of existing building and designate the use of each room, R106.1.
4. Specify fiber-cement board backing in tub/shower enclosures, R307.2, R702.4.2. (green board is no longer an acceptable backing)

STRUCTURAL PLANS:
5. Provide an attic space ventilation calculation (1:150) and note the size and location of all attic vents needed to comply, R806.2.

PLUMBING PLAN:
6. The Uniform Plumbing Code and the International Plumbing Code are not interchangeable. Only one of the two codes may be utilized per project.
7. Provide a fixture unit schedule for the entire property (including existing) for the water supply system with appropriate fixture unit values, UPC Tables 6-5.
8. Developed length of water supply line is measured from the meter to the furthest fixture served.
9. Water conservation requirements: Water closets = 1.6 gallons per flush, Sinks/ Showerheads = 3 gpm, UPC State Amend. 45-312.
10. Provide a complete gas piping layout and size the supply pipe for the connected demand. Include the length of line and BTU demand for each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, UPC 1217.0 Table 12-8.

MECHANICAL PLAN:
11. Show supply and return air ducts with a minimum R-8 insulation, R1103.2.1.

ELECTRICAL PLAN:
12. Provide an electrical load calculation for the existing panel to determine the service panel size, E3502.2.
13. GFCI protection is required for all receptacles located in garages, E3802.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2009 DELMA ROBEY OUT TO CUSTOMER Completed
06/19/2009 DELMA ROBEY REJECT SHELF Completed