09/22/2008 ROBERT SHERRY WATER REVIEW Denied Comment not addressed. Tucson Water limits a 2" meter to a maximum demand of 80 GPM. Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project Reference: Sections 610.2 and 610.12, UPC 2006
09/23/2008 MARTIN BROWN FIRE REVIEW Denied Comments not addressed.
Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.

Fire lane signage pg.x1.4 incorrect. Refer to 2006 IFC COT Modifications Appendix D for proper verbage.

Fire Department approved lock box required at south gate to cul-de-sa c. please refer to COT amendments to the 2006 IFC, Section 503.6.1 and 503.6.2 for details.
09/23/2008 GERRY KOZIOL WWM REVIEW Denied need DEQ review & approval to construct on-site private sewer for Rincon Vista Middle School. Need copy of on-site private sewer plan for base map update. need wastewater review of location/method of connection to on-site private sewer (joint use agreements, capacity & etc)