Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T08CM02657
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not addressed. Tucson Water limits a 2" meter to a maximum demand of 80 GPM. Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project Reference: Sections 610.2 and 610.12, UPC 2006 |
| 09/23/2008 | MARTIN BROWN | FIRE | REVIEW | Denied | Comments not addressed. Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. Fire lane signage pg.x1.4 incorrect. Refer to 2006 IFC COT Modifications Appendix D for proper verbage. Fire Department approved lock box required at south gate to cul-de-sa c. please refer to COT amendments to the 2006 IFC, Section 503.6.1 and 503.6.2 for details. |
| 09/23/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | need DEQ review & approval to construct on-site private sewer for Rincon Vista Middle School. Need copy of on-site private sewer plan for base map update. need wastewater review of location/method of connection to on-site private sewer (joint use agreements, capacity & etc) |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/01/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 10/01/2008 | SUE REEVES | REJECT SHELF | Completed |