Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02656
Parcel: 14101008C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM02656
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2008 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/17/2008 SREEVES1 ADA REVIEW Passed
09/18/2008 MARTIN BROWN FIRE REVIEW Denied Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.

Fire lane signage pg.x1.4 incorrect. Refer to 2006 IFC COT Modifications Appendix D for proper verbage.

Fire Department approved lock box required at south gate to cul-de-sa c. please refer to COT amendments to the 2006 IFC, Section 503.6.1 and 503.6.2 for details.
09/18/2008 RONALD BROWN ZONING HC SITE REVIEW Passed ACCESSIBILITY REVIEW BY THIRD PARTY, STANTEC
09/19/2008 ROBERT SHERRY WATER REVIEW Approved
09/19/2008 CPIERCE1 WWM REVIEW Needs Review
09/19/2008 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2008 CPIERCE1 OUT TO CUSTOMER Completed