Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T08CM02655
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2008 | SUE REEVES | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/17/2008 | SREEVES1 | ADA | REVIEW | Passed | |
09/18/2008 | MARTIN BROWN | FIRE | REVIEW | Denied | Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. Fire lane signage pg.x1.4 incorrect. Refer to 2006 IFC COT Modifications Appendix D for proper verbage. Fire Department approved lock box required at south gate to cul-de-sa c. please refer to COT amendments to the 2006 IFC, Section 503.6.1 and 503.6.2 for details. |
09/18/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Passed | ACCESSIBILITY REVIEW BY THIRD PARTY, STANTEC |
09/19/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/19/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
09/19/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/19/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |