Permit Number: T08CM02654
Parcel: 14101008C

Review Status: Completed

Review Details: SITE

Permit Number - T08CM02654
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2008 TERRY STEVENS ZONING REVIEW Passed
08/05/2008 RONALD BROWN ZONING HC SITE REVIEW Passed
08/05/2008 RBROWN1 ADA REVIEW Approved 6 AUGUST 2008
T08CM02654
REVIEWED BY RON BROWN

ACCESSIBLE REVIEW
ADAAG 1994 EDITION

DENIED: SEE COMMENTS BELOW

SHEET X1.2
1. All curb and side walk ramps to comply with ADAAG sections 4.7 and 4.8. Provide large scale details of all different types of ramps showing dimensions, slopes, accessible routes and detectable warnings.
a. Detectable warnings for all curb ramps to be in compliance with section 4.7.7 and sized accordingly.
b. Detectable warnings at all sidewalk ramps shall be in compliance with section 4.29.5 and sized accordingly
2. All accessible parking to comply with ADAAG section 4.1.2 (5) (a) and 4.6. Show large scale detail showing slopes, dimensions, "Van Accessible" spaces, curbs, ramps, detectable warnings, and accessible routes and etc
a. All detectable warnings to be placed at the end of all parking aisles as per section 4.29.5.
b. Provide a physical barrier at the front of all accessible parking spaces to comply with section 4.29.5.
c. Show "Van Accessible" space.
3. The crossing angle of all marked crossings, with exception of the most westerly crossing, presents a situation for physically and visually empaired persons that makes the already hazardous crossing even more hazardous because of their increased distance and additional time to cross as compaired to a perpendicular crossing. Please adjust these angles to something shorter, less hazardous and acceptable.
a. All ramps for crossings to comply with note 1 above.
4. Provide sign post detail for accessible parking and show locations of all signs on all site plan.
5. Detail 10/x1.4:
a. Contact "Park Wise" for exact sign format and graphic layout.
b. Provide a "Van Accessible" sign at identified van accessible spaces.
c. Fine is now $532.00
5. Identify accessible route through out new campus addition and connection to existing accessible route as required by ADAAG sections 4.1.2., 4.1.3, and 4.3

END OF REVIEW
08/07/2008 DAVE MANN FIRE REVIEW Approved
08/15/2008 ANDREW CONNOR NPPO REVIEW Passed
08/15/2008 ANDREW CONNOR LANDSCAPE REVIEW Passed
08/27/2008 PAUL MACHADO ENGINEERING REVIEW Passed