Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T08CM02618
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/31/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/31/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02618 7/31/08 1. From the line diagram it appears that there are 12 existing service disconnecting means, and the proposed addition of a 13th. This appears not to meet the requirements of NEC 230.2 Number of Services. 2. Please specify the line side and load side ratings the series system. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/27/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |