Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02615
Parcel: 132166300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02615
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02615 7/31/08

1. Conductor constant for 3/0 would be 12844, not 10400. Please rework fault calculations.
07/31/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/01/2008 DROBEY1 ZONING REVIEW Needs Review
08/01/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2008 DELMA ROBEY OUT TO CUSTOMER Completed