Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 6TH
Permit Number - T08CM02601
Review Name: REVISION - - 6TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/01/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show a vent for the floor drain in the mechanical room. 2. Clarify the 3/4" HWR line on the riser diagram 4/P-7.1; it does not appear to be shown on the plumbing plans. 3. Clarify the gas load for the pool and spa heaters. On sheet P-8.0 they are shown as 400 MBH each but on sheet P-8.1 they are shown as 1000 MBH for the pool heater and 400 MBH for the spa heater. 4. Show the gas piping for the three woks. |
| 12/01/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/04/2009 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/04/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |