Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show a vent for the floor drain in the mechanical room.
2. Clarify the 3/4" HWR line on the riser diagram 4/P-7.1; it does not appear to be shown on the plumbing plans.
3. Clarify the gas load for the pool and spa heaters. On sheet P-8.0 they are shown as 400 MBH each but on sheet P-8.1 they are shown as 1000 MBH for the pool heater and 400 MBH for the spa heater.
4. Show the gas piping for the three woks.
12/01/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
12/04/2009 GERRY KOZIOL WWM REVIEW Approved