Permit Number: T08CM02598
Parcel: 133231390

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02598
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2008 SREEVES1 WWM REVIEW Passed
08/01/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE PREVIOUS COMMENTS FROM 7-29-08 REVIEW.
2. SHEET A-03; EQUIPMENT PLAN: REMOVE REFERENCE TO ADAAG 7.2 (AT ACCESSIBLE COUNTER). USE ICC/ANSI A117.1-2003.
3. SHEET A-00; RESTROOM SIGNAGE 3a: LIST CURRENT ICC STANDARD.
08/08/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T0CM02598
7865 E Broadway Bl #105

The Electrical Plans for this project have been denied for the following reasons,

1.Show the water heater and the assigned circuits on the the power plan.
2.Show the freezer and assigned circuits on the power plan.
3.Show the bread oven and assigned circuits on the power plan.
4.Show the walk in and assigned circuits on the power plan.
5.Provide the interior lighting load calculations as per the 2006 IECC.


Ray T Majuta
DSD City of Tucson
Elect Plan Check
520-837/4988
8/11/08
08/12/2008 GERRY KOZIOL WWM REVIEW Denied NEEDS WASTEWATER 5TH FLOOR CREDIT EVALUATION
08/20/2008 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2008 DELMA ROBEY APPROVAL SHELF Completed
09/02/2008 DELMA ROBEY OUT TO CUSTOMER Completed
09/02/2008 GERARDO BONILLA REJECT SHELF Completed