Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02598
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/29/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/29/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/29/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/29/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. REMOVE ALL REFERENCES ON PLANS TO RESTROOM ACCESSIBILITY. 2. PER IBC SECTION 3409.7, PROVIDE COST BREAKDOWN, INDICATING THE COST OF PROVIDING ACCESSIBILITY (MAXIMUM 20%). GRAB BARS, ETC., MAY BE ADDED. 3. NO ACCESSIBILLITY SIGNAGE SHALL BE ADDED. 4. REFERENCE TO IBC 3409.6 IS INCORRECT. 5. REMOVE MINIMUM REQUIRED NEW DOOR OPENING CLEARANCES FROM SHEET A-03. |
| 07/29/2008 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 07/29/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/29/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/29/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/29/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |