Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02579
Parcel: 117150040

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T08CM02579
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2008 LOREN MAKUS ENGINEERING REVIEW Approved
07/25/2008 TERRY STEVENS ZONING REVIEW Approved
07/29/2008 MARTIN BROWN FIRE REVIEW Approv-Cond Design criteria for sprinkler system on sheet P1.1 is incorrect. Basement area is designated as "Storage". Labeled as Light Hazard, storage is Ordinary, Group 2 Hazard. Density for this area is .2 over 1500 sq. ft.
08/12/2008 CAGUILA1 ZONING HC SITE REVIEW Needs Review
08/12/2008 JOHN WILLIAMS BUILDING-COMMERCIAL REVIEW Needs Review
08/12/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/12/2008 WILLDAN ADA REVIEW Passed