Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM02578
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/10/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. ALL SECTIONS ON SHEETS A3-5, A3-6, AND A3-7, WITH THE EXCEPTION OF SECTION 2/A3-7, DO NOT REQUIRE BRACING BECAUSE THEY ARE SUPPORTED AT THE TOP AND BOTTOM OF THE WALL TO THE EXISTING STRUCTURE (THESE SECTIONS WERE NOT INCLUDED IN THE FIRST REVIEW). THAT DOES NOT REMOVE THE REQUIREMENT OF THE IBC SECTION 1607.13, STATING THAT ALL INTERIOR WALLS OVER 6' IN HEIGHT MUST BE ABLE TO RESIST A 5 PSF HORIZONTAL LOAD. THE WALL STUDS IN SECTION 2/A3-7 MUST BE BRACED TO THE EXISTING WOOD FLOOR STRUCTURE ABOVE, OR CALCULATIONS MUST BE PROVIDED INDICATING THE UNBRACED, CANTILEVERED WALL STUDS CAN RESIST THE CODE REQUIRED LOAD. TABLE 2308.9.1 IS A PRESCRIPTIVE GUIDELINE TO SIZING WALL STUDS, BUT IN NO WAY SUPERCEDES OR REPLACES THE REQUIREMENTS OF SECTION 1607.13. IN ADDITION, THE CONNECTIONS OF THE NEW TOP AND BOTTOM STUD WALL PLATES TO THE EXISTING STRUCTURE MUST BE DESIGNED AND INDICATED ON THE SECTIONS ON SHEETS A3-5, A3-6, AND A3-7. |
10/13/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/23/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. 2. Clarify how the spaces noted on the submitted spreadsheet correlate to the spaces shown on the plans. 3. The architect's floor plan has been changed, creating an unventilated corridor near the restrooms and janitor's closet. Clarify how the new corridor is to be ventilated |
10/23/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/23/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
10/28/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | NEEDS 5TH WASTEWATER 5TH FLOOR CREDIT EVALUATION |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/05/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
11/05/2008 | SUE REEVES | REJECT SHELF | Completed |