Permit Number: T08CM02578
Parcel: 11710075B

Address:
270 N CHURCH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02578
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. ALL SECTIONS ON SHEETS A3-5, A3-6, AND A3-7, WITH THE EXCEPTION OF SECTION 2/A3-7, DO NOT REQUIRE BRACING BECAUSE THEY ARE SUPPORTED AT THE TOP AND BOTTOM OF THE WALL TO THE EXISTING STRUCTURE (THESE SECTIONS WERE NOT INCLUDED IN THE FIRST REVIEW). THAT DOES NOT REMOVE THE REQUIREMENT OF THE IBC SECTION 1607.13, STATING THAT ALL INTERIOR WALLS OVER 6' IN HEIGHT MUST BE ABLE TO RESIST A 5 PSF HORIZONTAL LOAD. THE WALL STUDS IN SECTION 2/A3-7 MUST BE BRACED TO THE EXISTING WOOD FLOOR STRUCTURE ABOVE, OR CALCULATIONS MUST BE PROVIDED INDICATING THE UNBRACED, CANTILEVERED WALL STUDS CAN RESIST THE CODE REQUIRED LOAD. TABLE 2308.9.1 IS A PRESCRIPTIVE GUIDELINE TO SIZING WALL STUDS, BUT IN NO WAY SUPERCEDES OR REPLACES THE REQUIREMENTS OF SECTION 1607.13. IN ADDITION, THE CONNECTIONS OF THE NEW TOP AND BOTTOM STUD WALL PLATES TO THE EXISTING STRUCTURE MUST BE DESIGNED AND INDICATED ON THE SECTIONS ON SHEETS A3-5, A3-6, AND A3-7.
10/13/2008 MARTIN BROWN FIRE REVIEW Approved
10/23/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used.
2. Clarify how the spaces noted on the submitted spreadsheet correlate to the spaces shown on the plans.
3. The architect's floor plan has been changed, creating an unventilated corridor near the restrooms and janitor's closet. Clarify how the new corridor is to be ventilated
10/23/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/23/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
10/28/2008 GERRY KOZIOL WWM REVIEW Denied NEEDS 5TH WASTEWATER 5TH FLOOR CREDIT EVALUATION

Final Status

Task End Date Reviewer's Name Type of Review Description
11/05/2008 CPIERCE1 OUT TO CUSTOMER Completed
11/05/2008 SUE REEVES REJECT SHELF Completed