Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T08CM02567
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08CM02567 9/5/08 1. According to the fault calculations, the gutter is 130' from the meter and service disconnect. This is not shown on the plans. 2. New meter and disconnect barely legible on Sheet E-4. 3. Conduit to Panels A1 and A2 appears to originate at the new service disconnecting means on Sheet E-1, but according to the line diagram on Sheet E-4 these conduits originate at a gutter. Please locate the gutter on the plans such that the distances used in the fault calculations are verifiable. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/03/2008 | SUE REEVES | APPROVAL SHELF | Completed |
| 10/03/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |