Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02567
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/25/2008 | RBROWN1 | ADA | REVIEW | Passed | |
| 08/25/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02567 8/25/08 1. Please provide sizing for the Main Bonding Jumper, per the requirements of NEC 250.28 (D). 2. Please note that TEP publishes an available fault current of 75,100A for a 1200A, 3-phase, 120/208V service. 3. Distance to power company transformer scales out to be about 111', not 150. |
| 08/25/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
| 08/25/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/25/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |