Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02567
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/25/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that either the design of the battery room complies with section 1105.6, IMC 2005 or that there is not sufficient refrigerant in the room to qualify as a machinery room. 2. The ventilation of the battery room does not comply with Section 502.4.2, IMC 2006. If an alternate means of ventilating this room is planned, submit an appeal to the building official justifying the design. Reference: Section 105.2, IMC 2006. 3. Show how the condensate will be handled (i.e. show the size, route, and termination of the condensate drains). |
| 07/25/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/25/2008 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 07/25/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/25/2008 | RSHERRY1 | WWM | REVIEW | Passed | No plumbing fixtures |
| 07/25/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 08/25/2008 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/25/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 08/25/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |