Review Details: COMMERCIAL TI

Permit Number - T08CM02567
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2008 MARTIN BROWN FIRE REVIEW Approved
07/25/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that either the design of the battery room complies with section 1105.6, IMC 2005 or that there is not sufficient refrigerant in the room to qualify as a machinery room.
2. The ventilation of the battery room does not comply with Section 502.4.2, IMC 2006. If an alternate means of ventilating this room is planned, submit an appeal to the building official justifying the design. Reference: Section 105.2, IMC 2006.
3. Show how the condensate will be handled (i.e. show the size, route, and termination of the condensate drains).
07/25/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/25/2008 ROBERT SHERRY WATER REVIEW Passed
07/25/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/25/2008 RSHERRY1 WWM REVIEW Passed No plumbing fixtures
07/25/2008 JASON GREEN ENGINEERING REVIEW Approved
08/25/2008 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
08/25/2008 CPIERCE1 ZONING REVIEW Needs Review
08/25/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed