Permit Number: T08CM02566
Parcel: 133180080

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02566
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/31/2008 MARTIN BROWN FIRE REVIEW Approved
07/31/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02566 9/31/08

1. Provide electrical power for the new WH. Reference Sheet P.1.
2. Provide power for the new EF. Reference Sheet M.1.
3. Since the new panel is being located closer to the electrical service than the panel it is to replace, please provide fault calculations at this panel and its fault current rating.
07/31/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/31/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved