Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM02566
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/31/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/31/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/31/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02566 9/31/08 1. Provide electrical power for the new WH. Reference Sheet P.1. 2. Provide power for the new EF. Reference Sheet M.1. 3. Since the new panel is being located closer to the electrical service than the panel it is to replace, please provide fault calculations at this panel and its fault current rating. |
07/31/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/31/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |