| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/31/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/31/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02566 9/31/08 1. Provide electrical power for the new WH. Reference Sheet P.1. 2. Provide power for the new EF. Reference Sheet M.1. 3. Since the new panel is being located closer to the electrical service than the panel it is to replace, please provide fault calculations at this panel and its fault current rating. |
| 07/31/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/31/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |