Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02542
Parcel: 14111027A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM02542
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/15/2008 JWILLIA5 ZONING HC SITE REVIEW Passed
10/15/2008 JWILLIA5 ADA REVIEW Passed
10/16/2008 TERRY STEVENS ZONING REVIEW Denied 10/16/2008

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
10/17/2008 DAVE MANN FIRE REVIEW Approved
10/22/2008 GERRY KOZIOL WWM REVIEW Denied need to review location & method of connection to public sewer
10/22/2008 JASON GREEN ENGINEERING REVIEW Denied DATE: October 22, 2008
SUBJECT: 7575 S Old Vail Road Building Plan- Engineering Review
TO: John Feneck
LOCATION: T15S R15E Sec21 Ward 4
REVIEWERS: Jason Green, CFM
ACTIVITY: T08CM02542 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T08CM02542) for the above referenced property. Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved development plan. Please submit two copies of the stamped approved development plan, landscape, and NPPO plans with the next building plan submittal. Engineering may not be able to approve the building plan until the development plan has been approved.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide a revised building plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon re-submittal of the building plan review.

If you have any questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
10/29/2008 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2008 SUE REEVES OUT TO CUSTOMER Completed