Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T08CM02521
Review Name: RESUBMITTAL
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/23/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/26/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
01/26/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/27/2009 | TERRY STEVENS | ZONING | REVIEW | Denied | 01/27/2009 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming. |
01/28/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. WALMART 2. NEED TO BUILD PUBLIC SEWER - NEEDS 8TH FLOOR WASTEWATER PUBLIC SEWER CONTRUCTION PERMIT - NEEDS DSC/WW/1ST FLOOR HOLD HARMLESS LETTER 4. NEED TO PERMIT ON - SITE PRIVATE SEWER - NEED DEQ REVIEW & APPROVAL TO CONSTRUCT ON - SITE PRIVATE SEWER 5. NEED COPY OF ON - SITE PRIVATE SEWER FOR BASE MAP UPDATE |
02/09/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/10/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved, see Section 202 (Indirectly conditioned space), IECC 2006 as amended by the City of Tucson. The minimum insulation for ducts located in indirectly conditioned spaces within the building envelope is R-4.2 (installed). Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 2. Comment not resolved; the exhaust fan shall run whenever supply air is introduced into the restroom. Provide information on the sequence of operation for the pharmacy restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. 3. Comment not resolved; deferred submittals for kitchen hoods are not acceptable. Provide the operating weights for the exhaust hoods and their associated exhaust fans. Reference: Section 106.3.1, IMC 2006. 4. Comment not resolved; deferred submittals for kitchen hoods are not acceptable. Provide structural calculations and details to show that the Type I and Type II hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006. |
02/10/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Complete the waste and vent isometrics (sheet GP3) for the grocery area by indicating the trap sizes and the pipe sizes. Reference: Sections 103.2.3 and 910.0, UPC 2006. 2. Comment not resolved, the maximum length for a 4" tailpiece is 10 feet. Provide justification for the 18-foot long horizontal tailpiece for the floor drain at the compactor pad. Reference: Section 103.2.3, UPC 2006. 3. The presence of manholes in the private sewage system for this activity mandates a review by the Pima County Department of Environmental Quality. The design for the system must be submitted to the Pima County Department of Environmental Quality for their approval prior to obtaining a permit for constructing the sewage collection system from the City of Tucson (this permit is separate from the building permit). Reference: A.R.S. 49-104 (B) (13) |
02/17/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/18/2009 | SUE REEVES | REJECT SHELF | RECEIVED |