Permit Number: T08CM02504
Parcel: 11714151A

Address:
485 S MAIN AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02504
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2008 HEATHER THRALL ZONING REVIEW Needs Review
07/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/18/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02504 7/18/08

1. TEP SR-510 specifies that for overhead commercial single phase services one must contact the company for available fault current. Please do this, or add a note to the plans requiring the Contractor to do so before ordering the new panel. COMMENT SATISFIED, PER LAB, 8/1/08.
2. New overhead electrical services need to have a waiver from the City of Tucson. Please fill out the attached form and turn it in to DSD Administration.
07/18/2008 ROBERT SHERRY WATER REVIEW Approved
07/18/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE STRUCTURAL CALCULATION FOR ROOF JOISTS WHERE NEW RTU (HEAT PUMP) IS LOCATED.
07/18/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
07/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/18/2008 DAVE MANN FIRE REVIEW Approved
08/20/2008 VFLORES1 ENGINEERING REVIEW Needs Review
08/20/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review