Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02504
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/18/2008 | HEATHER THRALL | ZONING | REVIEW | Needs Review | |
07/18/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
07/18/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02504 7/18/08 1. TEP SR-510 specifies that for overhead commercial single phase services one must contact the company for available fault current. Please do this, or add a note to the plans requiring the Contractor to do so before ordering the new panel. COMMENT SATISFIED, PER LAB, 8/1/08. 2. New overhead electrical services need to have a waiver from the City of Tucson. Please fill out the attached form and turn it in to DSD Administration. |
07/18/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/18/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE STRUCTURAL CALCULATION FOR ROOF JOISTS WHERE NEW RTU (HEAT PUMP) IS LOCATED. |
07/18/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
07/18/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
07/18/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
08/20/2008 | VFLORES1 | ENGINEERING | REVIEW | Needs Review | |
08/20/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |