Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02481
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02481 7/22/08 1. Ckt 30 has lighting fixtures according to the Lighting Plan, but the WH according to the Power Plan and Panel Schedule. Pls clarify. 2. Show existing location of relocated Panel CU. |
07/22/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
07/22/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |