Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T08CM02440
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2008 | MARTIN BROWN | FIRE | REVIEW | Denied | Please show location of existing and proposed fire hydrants. Refer to C.O.T. amendments to the 2006 IFC for spacing requirements. Fire sprinklers will be required. Show location of fire service. |
| 07/14/2008 | TERRY STEVENS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Terry Stevens Lead Planner PROJECT: T08CM02440 1106 N. Camilla Blvd. Site Plan TRANSMITTAL DATE: 07/15/08 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. DS 2-02.2.1.4 A small, project-location map shall be drawn on the first sheet of the development plan, preferably in the upper right corner. The map should cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile, and provide the following information. " Show the subject property approximately centered within the one (1) square mile " area. " Identify conditions within the square mile area, such as major streets and " watercourses. " Section, township, and range; section corners; north arrow; and the scale will be " labeled. 2. DS 2-02.2.1.7 Per LUC Sec. 3.2.3.1.D this project has a perimeter yard indicator of "CC". Per LUC Sec. 3.2.6.4 the required setback when adjacent to a C-2 zoned property is the height of the structure. The covered parking structure and the proposed building do not meet this requirement for setbacks from the south property line based on a wall height of 17'-4" for the proposed building and say an approximate 9' height for the carport. Revise the perimeter yard notes on page C-1 to indicate the correct required setbacks. 10' or ¾ the height where adjacent to R-3 zoned property, height of the structure where adjacent to commercial zoned property. Provide dimensioned building elevations for the proposed building and the covered parking structure in order to verify the required setbacks. Clearly indicate the required 98" vertical clearance for the covered handicap parking spaces. Per ICC/ANSI 117.1-2003 Sec. 502.6. 3. DS 2-02.2.1.9 Please provide dimensioned details for class 1 and class 2 bicycle parking racks and enclosures. Please provide a plan view detail of the proposed class 2 bicycle parking spaces. Single rack spaces placed in a row will allow a minimum of seventy -two (72) inch length per bicycle parking space and a minimum of thirty (30) inches between outer spaces of racks. 4. DS 2-02.2.1.11 Per DS 3-05.2.2.B.2 A minimum distance of one (1) foot must be maintained between any open structure, such as a carport, and a PAAL. The one (1) foot setback is conditioned upon the pedestrian way(s) being designed at a location other than between the open structure and the PAAL. The distance is measured to the closest part of the structure, i.e., a roof overhang. Clearly indicate with dimensions the one foot setback from the PAALs for all covered parking structures. Along the south property line there appears to be a drafting error in regards to the location of the vertical curbing and the location of the wheel stops. Revise. 5. DS 2-02.2.1.12 The pedestrian circulation path cannot be located behind a vehicle parking space (parking spaces near the trash enclosure). See DS 2-08.4.1.F Sidewalks or pedestrian refuge areas may not be located between any motor vehicle parking space and the PAAL providing access to that space. Provide a pedestrian circulation path to the trash enclosure. See DS 2-08.3.1. 6. DS 2-02.2.1.20 Provide recordation information (docket and page) for the abandonment of the indicated ingress, egress and sewer easement. 7. DS 2-02.2.1.21 If applicable, provide the proposed lighting layout and type. 8. DS 2-02.2.1.31 In the proposed use note add the subject to section after the use. Should read as follows: Family Dwelling subject to: 3.5.7.1.F 9. This site contains two (2) separate parcels therefore you will need to provide a Pima County Tax Parcel Combo. Provide documentation of the approved tax parcel combination. If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961 C:\planning\cdrc\DSD\T08CM02440.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 07/21/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | 22 JULY 2008 T08CM0240/CAMILLA PLACE REVIEWED BY RON BROWN ACCESSIBLE REVIEW 2006 IBC/ICC 117.1 DENIED: SEE COMMENTS BELOW A. DENOTE GOVERNING ACCESSIBILITY CODES ON TITLE SHEET OF PLANS; 2006 IBC, CHAPTER 11 AND ICC 117.1 FOR PRIVATE PROPERTY AND RIGHT OF WAY ACCESSIBILITY STANDARDS; COT DOT STANDARDS FOR CURB RAMPS AT DRIVE WAY ENTRANCE FROM STREETS. 1. NOTE ONE OF THE TWO ACCESSIBLE SPACES TO BE "VAN ACCESSIBLE" B. IDENTIFY ACCESSIBLE ROUTE ON SITE PLAN AND SHOW LOCATION OF NEAREST PUBLIC TRANSPORTATION POINT AS PER 2066 IBC, SECTION 1104 AND ICC 117.1, SECTION 402. C. PROVIDE ACCESSIBLE PARKING SIGN DETAIL, 7' ABOVE GRADE TO BOTTOM OF SIGN. D. THE MARKED CROSSING IS LOCATED IN THE BACK OF A PARKING SPACE WHERE AUTOS WILL BACK UP DIRECTLY ONTO THE ACCESSIBLE ROUTE. RECONFIGURE THIS PARKING SPACE PARALLEL TO MARKED CROSSING. E. PROVIDE A NOTE ON DRAWING THAT FUTURE DEVELOPMENT WILL COMPLY WITH THE INCLUSIVE HOME DESIGN ORDINANCE NUMBER 10463. F. PROVIDE OCCUPANCY CLASSIFICATION ON COVER SHEET AS PER 2006 IBC, CHAPTER 3. G. ON SHEET 3, CHANGE NOTE REFERENCE DOT 207 TO IBC 2006/ICC 117.1, SECTIONS 405 AND 406. H. ONE ACCESSIBLE PARKING SPACE MUST BE "VAN ACCESSIBLE" AND MUST BE 11' WIDE WITH A 5' WIDE AISLE. END OF REVIEW |
| 07/23/2008 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Denied | 1. Revise the landscape plan to show the extent of supplementary irrigation in each planting area provided by water harvesting methods. Show the amount and disposition of flow and indicate drainage points from buildings and paved areas. DS 2-07.2.2.C 2. Any changes made to the site plan must be reflected on the landscape plan. |
| 07/24/2008 | PETER MCLAUGHLIN | NPPO | REVIEW | Approved | Exception approved. |
| 08/11/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | August 15, 2008 Camilla Place T08CM02440 1. A grading permit is required for this project. The grading plan and permit application may be submitted with the site plan when it is re-submitted. 2. Provide the correct locations for details called out in the large plan views of the site. 3. Clarify the ownership of the existing walls along the east property boundary. One of the walls is on the adjacent property. If new holes are to be made in the walls, provide authorization from the owner of the adjacent property. If the holes are existing, indicate that on the plan. 4. Darken the existing contours and ensure that they are labeled so existing and proposed grades can be compared. 5. Revise the drainage scheme to maximize water harvesting. Explain how the concrete channel will facilitate water harvesting. Ensure that the Landscape plans and the site/grading plans are consistent. 6. Revise the drainage report to provide a correct description of the project location. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/21/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 08/21/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/21/2008 | GERARDO BONILLA | REJECT SHELF | Completed |