11/05/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM02437 Rev 11/12/08

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" All code references to the International Residential Code shall be changed from 2003 to 2006. Revise the code reference at sheet T1.0.
" Sheet A1.1 is listed on the Index but is missing from the last submittal.

FLOOR PLANS:

1. Show compliance with R310 providing egress from Bedroom 2 without passing through another room. The bath area (with escape) can be considered an extension of the bedroom if the common wall is a minimum of 50% open.

STRUCTURAL PLANS:

1. Note the size and weight of roof mounted equipment on the Roof Framing Plan (sheet A4.1) required for the truss design, M1401.
2. Revise the truss calculations to include the Solar Panel loading with cross-referencing to the plans, R802.10.2.

PLUMBING PLANS:

1. Show the service pipe and branch lines in compliance with IRC P2903.6. A dwelling with 34.9 fixture units requires a 1" water meter and a 1-1/4" service pipe. Branch pipes may be reduced in size as the downstream fixture count allows, Table P2903.7.

ELECTRICAL PLANS:

1. A (floor) receptacle outlet is required within 18" of the fixed glass panel more than 6' from the door opening, E3801.2. Add or relocate the floor receptacle between the fireplace and Great Room exterior doors.
2. Provide the Solar Panel and Inverter specification sheets for the Photovoltaic System, City of Tucson Photovoltaic Template.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show a U-value for the field assembled skylights, a REScheck report is necessary for single layer theromopane glass, N1101.2.