Permit Number: T08CM02434
Parcel: 107020130

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T08CM02434
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2008 STEVE SHIELDS ZONING REVIEW Approved
10/22/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved Note: Clearly indicate that there is one way traffic along east property line. Provide proper signage.
10/27/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The finished floor elevation (2294.08') is below the elevation of the next upstream manhole in the public sewer (2294.70'); provide a backwater valve in the building sewer. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2008 CPIERCE1 OUT TO CUSTOMER Completed
10/28/2008 SUE REEVES REJECT SHELF Completed