Permit Number: T08CM02426
Parcel: 12404100A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02426
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
07/11/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
07/11/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied ELECTRICAL PLAN CHECK RTMAJUTA,DSD, 7/11/08

1. PROVIDE A ONE LINE DIAGRAM OF SERVICE INDICATING EXISTING SERVICE LOAD PLUS NEW LOAD FOR THIS SPACE.
2.CANNOT LOCATE CIRCUIT 26.
3. IS A NEW LIGHTING CONTROL PANEL TO BE ADDED ? PLEASE PROVIDE INFO ON THIS
07/11/2008 ROBERT SHERRY WATER REVIEW Approved
07/11/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
07/14/2008 CPIERCE1 ENGINEERING REVIEW Approved See grading plan for floodplain delineation.
07/14/2008 CPIERCE1 ZONING REVIEW Needs Review
07/14/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/14/2008 MARTIN BROWN FIRE REVIEW Approved
07/15/2008 CPIERCE1 WWM REVIEW Needs Review