Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02426
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/11/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/11/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | ELECTRICAL PLAN CHECK RTMAJUTA,DSD, 7/11/08 1. PROVIDE A ONE LINE DIAGRAM OF SERVICE INDICATING EXISTING SERVICE LOAD PLUS NEW LOAD FOR THIS SPACE. 2.CANNOT LOCATE CIRCUIT 26. 3. IS A NEW LIGHTING CONTROL PANEL TO BE ADDED ? PLEASE PROVIDE INFO ON THIS |
| 07/11/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/11/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 07/14/2008 | CPIERCE1 | ENGINEERING | REVIEW | Approved | See grading plan for floodplain delineation. |
| 07/14/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 07/14/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 07/14/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/15/2008 | CPIERCE1 | WWM | REVIEW | Needs Review |