Permit Number: T08CM02395
Parcel: 117060940

Address:
55 N 5TH AV

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM02395
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2009 ROBERT SHERRY WATER REVIEW Approved
02/23/2009 TERRY STEVENS ZONING REVIEW Denied 02/23/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
02/24/2009 MARTIN BROWN FIRE REVIEW Denied The building now appears to be a highrise per IBC Section 403. A large covered assembly area has been added to the mechanical and storage areas originally shown on the roof. Justify or comply with 403. The occupancy is shown as 174 on Sheet A0.02 and 222 on Sheet A0.03.

Provide a rail or wall on the exit across the roof or increase the live load for the whole roof section the exit crosses to 100 psf.
02/25/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/25/2009 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2009 CPIERCE1 OUT TO CUSTOMER Completed
03/03/2009 SUE REEVES REJECT SHELF Completed