Permit Number: T08CM02382
Parcel: 116192320

Address:
310 W ALAMEDA ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM02382
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/15/2008 DAVE MANN FIRE REVIEW Approved
07/16/2008 LOREN MAKUS ENGINEERING REVIEW Passed SEE PREVIOUS WORKFLOW
07/21/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/23/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Plan Check
For 310 W Alameda St , T08CM02382

The following items need to be addressed,

1. Provide service receptacles for HVAC equipment on roof as required in NEC 2005 210-63, and circuit according.

2. Several of the existing panels feeding from MSWB-1
on sheet E2-0 are labeled 120/208v and should be
277/480V.


Ray T Majuta
Electrical Plan Check
City of Tucson DSD
7/26/08, 520/837/4988
08/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used.
2. Clarify how the use of the ASHRAE 62.1-2004 category, "General / Storage Rooms", is appropriate for a printing zone. Reference: Section 106.3.1, IMC 2006.
3. Provide information to clarify how the replacement HVAC units compare to the existing HVAC units for weight and what, if any, structural changes are to be made to the roof framing. Reference: Section 3021, IMC 2006.
4. Indicate the proposed locations of the new duct smoke detectors. Reference: Sections 106.3.1 and 606.2, IMC 2006.
5. Provide a minimum R-value of R-8 for the wrapped exterior ductwork; paragraphs 2.02A and 3.03A, Section 15080 of the mechanical specifications provide an R-value of only 7.4 h*ft^2*F/Btu.
6. Provide fire/smoke dampers for the penetration of the return air shafts. Specify the required rating for the dampers. Reference: Sections 106.3.1 and 607.5.5, IMC 2006.
08/06/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the F- and T-rating required for the penetration of the shaft by the natural gas pipe and show how the pipe is to be supported on either side of the penetration. (Note: the installer shall provide documentation of the approved penetration system being used for the field inspector to compare with the actual installation.) Reference: Section 1501.1, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2008 VFLORES1 OUT TO CUSTOMER Completed