07/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM02338 7/8/08

1. It appears that circuit D-1 is overloaded. (21) 96-W fixtures at continuous loading would be 21a.
2. Ckt D-7 has receptacle load on the Power Plan, but the panel schedule attributes this circuit to lighting only. Please clarify.