Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/08/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08CM02338 7/8/08 1. It appears that circuit D-1 is overloaded. (21) 96-W fixtures at continuous loading would be 21a. 2. Ckt D-7 has receptacle load on the Power Plan, but the panel schedule attributes this circuit to lighting only. Please clarify. |