Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02338
Parcel: 10819277A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02338
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM02338 7/8/08

1. It appears that circuit D-1 is overloaded. (21) 96-W fixtures at continuous loading would be 21a.
2. Ckt D-7 has receptacle load on the Power Plan, but the panel schedule attributes this circuit to lighting only. Please clarify.
07/09/2008 GERRY KOZIOL WWM REVIEW Approved
07/09/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2008 DELMA ROBEY OUT TO CUSTOMER Completed