Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02307
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/24/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The sanitary riser diagram and the plumbing fixture schedule have the service sink labeled as P3 but the plumbing plan shows the sink as P4. Provide an upper terminal cleanout for the service sink and coordinate the fixture labels. Reference: Section 707.4, UPC 2006. 2. The specified lavatory faucet (Symmons model S-70-g) is called out as a "metering faucet without temperature selection" because it can only set the proportions of the hot and cold water supplies, not the delivery temperature. Show how the temperature of the hot water supply to the public lavatory is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
| 07/24/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02307 7/24/08 1.Feeder size for new Transformer is given as #6 on Dry Type Transformers Schedule. This is #1 per Power Riser Note 3. 2. Show fault calculations for Panel H. |
| 07/24/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/13/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/13/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |