Permit Number: T08CM02307
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02307
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/24/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The sanitary riser diagram and the plumbing fixture schedule have the service sink labeled as P3 but the plumbing plan shows the sink as P4. Provide an upper terminal cleanout for the service sink and coordinate the fixture labels. Reference: Section 707.4, UPC 2006.
2. The specified lavatory faucet (Symmons model S-70-g) is called out as a "metering faucet without temperature selection" because it can only set the proportions of the hot and cold water supplies, not the delivery temperature. Show how the temperature of the hot water supply to the public lavatory is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
07/24/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02307 7/24/08

1.Feeder size for new Transformer is given as #6 on Dry Type Transformers Schedule. This is #1 per Power Riser Note 3.
2. Show fault calculations for Panel H.
07/24/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/13/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2008 DELMA ROBEY OUT TO CUSTOMER Completed