Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02305
Parcel: 11507014A

Address:
20 E LESTER ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02305
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/03/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved