Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM02291
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2009 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS Date: 3-24-09 Activity: T08CM02291 Address: 5602 E. 25th Street Applicant: Rick Young Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: 1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. 2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. 3. Provide a letter of authorization from the engineer of record for the Amerimax design or provide a set of current stamped drawings. STRUCTURAL PLANS: 4. Specify a minimum opening of 22" by 30" for access and ventilation between over-framed assemblies, R807. PLUMBING PLAN: 5. Provide a water fixture unit schedule for the entire property (including existing) P2903.6. 6. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water service line, P2903.7. 7. The Tucson Water policy adopted 3/2/07 limits the maximum demand for a 5/8" water meter (there are no ¾" meters for Tucson Water service) to 10GPM, confirm with Tucson Water that the existing meter will be able to meet the new water demand. Reference Tables P2903.6 and P2903.6(1), IRC 2006. If you have any questions please contact: Clayton Trevillyan 520.837.4913 Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/25/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 03/25/2009 | SUE REEVES | REJECT SHELF | Completed |