Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM02290
Parcel: 10707003C

Address:
1185 W GLENN ST

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T08CM02290
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2008 JOHN WILLIAMS BUILDING-COMMERCIAL REVIEW Needs Review
07/01/2008 STEVE SHIELDS ZONING_QA REVIEW Passed
07/01/2008 STEVE SHIELDS ZONING REVIEW Needs Review
07/01/2008 BIANCA RAMIREZ ENGINEERING_QA REVIEW Passed
07/01/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/01/2008 CAGUILA1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/01/2008 CINDY AGUILAR OUT TO CUSTOMER Completed