Permit Number: T08CM02288
Parcel: 120063210

Address:
4301 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T08CM02288
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: April 23, 2009
SUBJECT: Site Only
TO: Jaca Design
LOCATION: 4301 S 6th Ave, T14S, R13E, Section 36, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM02288 (Third Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the site plan.

Site Plan:

1. Complied
2. Complied
3. Complied
4. Complied
5. Verify that all Sight Visibility Triangles have been labeled and depicted correctly per D.S. 2-02.2.1.10. Label site visibility triangles on each sheet. Provide SVTs for driveway along
6. Complied
7. Complied
8. Please provide Drainage patterns and finished grades on site plan per D.S. 2-02.2.1.16.
9. Complied
10. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations proposed buildings at pedestrian circulation areas. A detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk is required; refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk. Provide this information on the site plan.
11. Complied
12. DS Sec.2-02.2.1.A.19: Label the 9-foot future sidewalk and curb area on the site plan to verify that all improvements are located outside of the future ROW. Verify that the dimensions are called out on each sheet. Add label that states future sidewalk on future site plan.
13. Complied
14. Complied
15. Complied
16. Complied
17. Complied
18. Complied
19. Complied
20. Complied
21. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
22. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the grade break at the driveway, if applicable. Call out the height of the curb on the site plan within the details.
23. Complied
24. Complied
25. Complied
26. Complied
27. Complied
28. Complied
29. Complied
31. Acknowledged
32. Verify that sidewalk dimensions called out on site plan(s) match.
33. Complied
34. Label curb on site plan.
35. Dimension setback from water harvesting areas to proposed building.
35. Additional comments may be forthcoming.

Hydrologic/Hydraulic Report:

1. Complied
2. Complied
3. Complied
4. Complied
5. Complied
6. Provide Geotechnical Report for minimum setback recommendations and perc tests. Provide setback from the building and have distance called out on site plan.
7. Revise drainage report and project design to meet the minimum critical basin requirements per 10-01.2.1. Detention is required; show calculations for water harvesting that demonstrate that water harvesting areas will suffice. Show that water harvesting calculations are in accordance with the Water Harvesting Guidance Manual (p. 28-31).
8. Additional comments may be forthcoming.


If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax